Item specifics
-
Brand Name
samwhadsp
-
Certification
CE
-
Origin
CN(Origin)
-
Theory
Voltage Relay
-
is_customized
Yes
-
Contact Load
Low Power
-
Voltage
220V
-
Model Number
DGK-01
-
Protect Feature
Sealed
-
Power Source
AC
-
Usage
Protective
-
Protection Item 1
Overvoltage
-
Protection Item 2
undervoltage
General DGK-01 and DGK-01W voltage control relays are designed to block monophse loads malfunctions arising from network. Usage and Working Principle To set the high voltage value: set the "U>" control knob to the desired value.
To set the low voltage value: set the "U<" control knob to the desired value.
To set the delay time: set the "t" control knob to the desired value.
The set values is displayed on the display when adjusting with the setting knobs.2 seconds after releasing the set knob then on the display shows the measured voltage value.
If the voltage is between the set high "U>" and low "U<" voltage set values, the "Out" LED turns on and the relay is energised. Protection Functions High Voltage Protection - To enter the error state: lf the voltage goes above the high voltage set value, the "U>" LED is on, the device waits until the set delay time "t", after the time has elapsed the relay gets de-activated and the "Out" LED is off.
High Voltage Protection - Exiting the error state: When the voltage drops below 5V of the high voltage set value, the device waits for the delay time "t". After the time passes, the "U>" LED is off, the relay gets activated and the Out LED is on.
Low Voltage Protection - To enter the error state: lf the voltage goes below the low voltage set value, the "U<" LED is on, the device waits until the set delay time "t", after the time has elapsed the relay gets de-activated and the "Out" LED is off.
Low Voltage Protection - Exiting the error state: When the voltage goes above 5V of the low voltage set value, the device waits for the reset time "t". After the time passes, the "U<" LED is off, the relay gets activated and the "Out" LED is on.
Relay States Relay is Activated: 2(COM) and 3(NO) close, 1(NC) and 2(COM) open. Relay is de-activated: 2(COM) and 1(NC) close, 3(NO) and 2(COM) open. Maintenance Switch off the device and release from connections. Clean the trunk of device with a swab. Don’t use any conductor or chemical might damage the device. Make sure device works after cleaning Warnings Please use the device according to the manual. Don’t use the device in wet. Include a switch and circuit breaker in the assembly. Put the switch and circuit breaker nearby the device, operator can reach easily. Mark the switch and circuit breaker as releasing connection for device. Specifications Operating Voltage(Un)....: 220V AC Operating Frequency.......: 50/60 Hz. Operating Power...............: <6VA Operating Temperature..: -20°C.....+55°C High Voltage Set(U>)...........: 230V - 280V Low Voltage Set(U<)............: 150V - 210V 110V-210V(On the DGK-01W) Waiting (t).......................: 0,1sec - 10sec. Display.....................: 3x LEDs, 1x3 digit display Connection Type.....: Terminal connection Contact.................:5A/250V AC (Resistive Load) Cable Diameter.................: 2,5mm² Weight................................: Max. 220gr. Mounting...........................: Vertical assembled in the panel or assembled on the din rail Operating Altitude..........: <2000meter Dimensions  Connection diagram    |