Item specifics
Product Description
40A 63A 80A 230V 50/60Hz Din Rail Adjustable Automatic Recovery Over And Under Voltage Protector Voltage Protective Device Functions:1.Over-voltage protection2.Under-voltage protection3.Automatic recovery4.Volt-meterWe have the manual in English,Russian and Portuguese,tell us your e-mail address then we will send it to you.Product Parameters:1.Model number:SVP9122.Power supply:230VAC 50/60Hz3.Max.Loading power:40A/63A/80A4.Over-voltage protection value range:221V~300~OFF(default:280V)Over-voltage recovery voltage range:220V--299V(default:250V)Over-voltage protection action time:0.1s~10s(default value:0.1s)5.Under-voltage protection value range:219V--150V --OFF(default:160V)Under-voltage recovery voltage range:151V--220V (default:180V)Under-voltage protection action time:0.1s~10s(default:0.1s)6.Recovery delay time:2s~512s(default:60s)7.Delay time after power-on:2s~255s(default:2s)8.Power consumption : <2W9.Electric machinery life : 100,000 times10.Installation:35mm DIN railNoted: When you first connect the product, you have to wait about 1 minute, after the red light turn off, then the product will work. ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |